Extra functionality, faster testing, and as rugged as ever
The new 1650B Series builds on the rugged reputation of the earlier 1650 Series, only it’s re-designed to meet your need for more productive test tools.
This new series contain the following new features:
- Fast high current loop test
- Variable RCD current mode for customized settings
- PASS/FAIL indication for RCD tests
- FLUKE-1651 with 250 V insulation test voltage (250 V, 500 V and 1000 V)
- Select voltage measurement between L-N, L-PE and N-PE
- Zero adapter for easy test lead compensation, available as new accessory and also included with standard scope of supply
|
|
|
|
|
Fast loop measurement. (Saves up to 50% time!)
|
Lightweight (Weighs less than 1.2kg)
|
Rugged (withstands a drop from 1m)
|
- Fluke 1651B: The everyday tester, for every electrical installer
The everyday tester ideal for the domestic covering all the basic needs for testing to the 17th Edition wiring regs / Part P of the building regulations.
- Fluke 1652B: The ideal tester for professional trouble-shooters
Due to its additional functionality the Fluke 1652B is the ideal tester for professional trouble-shooters working in both domestic and commercial. Although packed with advanced features the 1652 is easy to through its intuitive user interface.
- Fluke 1653B: The complete tester for advanced users
The complete tester for virtually all electrical wiring installations - domestic, commercial or industrial. This is the instrument that has it all, all the test functions you need (including phase rotation test) to in-built memory for documenting results. The Fluke 1653B makes it the complete solution for professionals who need to have the best tool available.
|
|
|
Safer, easier installation testing.
The 1650B Series testers verify the safety of electrical installations in domestic, commercial and industrial applications. They can ensure that fixed wiring is safe and correctly installed to meet the requirements of IEC 60364, HD 384 and all relevant local standards
Faster
- Two measurements at once and a dual display.
PEFC/PSC and loop impedance are measured and displayed in parallel, saves you more than 50% of test time compared to other loop testers.
- Additional new high current loop mode. Faster measurements compared to loop tests with non-trip
mode for RCD’s.
- Unique zero adapter for fast, always reliable and accurate test lead and mains cord compensation.
- Fast voltage measurement between L-N, L-PE and N-PE using the mains cord. No need to change measurement connections.
|
Safer
- Earth Volt Touchpad detects raised earth voltages >50 V, indicating potential dangerous situations.
- Standard supplied with fused test leads to comply with GS38.
|
Easy
- Rotary dial knob indicates clear which function is selected, all functionalities on one spot and no complex multi level menus.
- Large display with backlight, clear symbols and with exceptionally wide viewing angle for easy and safe readings.
- PASS/FAIL indication for RCD test results.
- Variable RCD current mode for customized settings.
|
Rugged & lightweight
- Withstands a drop of 1 meter.
- Compact, lightweight (less than 1.2 kg) and padded neck-strap to free your hands for all day testing.
|
|
Complete kit All 1650B models are equipped with detachable leads that can be replaced in case of damage or loss. A durable hard case will protect your instrument in tough field conditions.
|
|
Slim probe design with test button Keeps your eyes on the panel while probing hard to reach points. This remote probe is powered by the tester so always operable (does not require additional batteries).
|
|
Zero Adapter For easy, always reliable and accurate compensation of test leads and mains cords. This adapter can be used for all
different kind of mains plugs as well as test accessories like probes, alligator clips etc.
|
|
| Specifications |
| AC Voltage Measurement |
| Range: |
500 V |
| Resolution: |
0.1 V |
| Accuracy (50 - 60 Hz) |
± (0.8% + 3 digits) |
| Input Impedance |
3.3 MΩ |
| Overload Protection |
660 Vrms |
| | Continuity Testing |
| Range (autoranging): |
20 Ω, 200 Ω, 2000 Ω |
| Resolution: |
0.01 Ω, 0.1 Ω, 1 Ω |
| Test Current: |
> 200 mA |
| Open Circuit Voltage: |
> 4 V |
| Accuracy: |
± (1.5%+3 digits) |
| | Insulation Resistance Measurement |
| Test Voltage: |
|
| Fluke 1651B: |
250 - 500 - 1000 V |
| Fluke 1652B: |
250 - 500 - 1000 V |
| Fluke 1653B: |
50 - 100 - 250 - 500 - 1000 V |
|
|
| |
|
| Test Voltage: |
50 V |
| Test Current: |
1 mA @ 50 kΩ |
| Insulation Range: |
10 kΩ - 50 мΩ |
| Resolution: |
0.01 мΩ |
| Accuracy: |
± (3% + 3 digits) |
| |
|
| Test Voltage: |
100 V |
| Test Current: |
1 mA @ 100 kΩ |
| Range/Resolution: |
20 MΩ/0.01 MΩ |
| Range/Resolution: |
100 MΩ/0.1 MΩ |
| Accuracy: |
± (3% + 3 digits) |
| |
|
| Test Voltage: |
250 V |
| Test Current: |
1 mA @ 250 kΩ |
| Range/Resolution: |
20 MΩ/0.01 MΩ |
| Range/Resolution: |
200 MΩ/0.1 MΩ |
| Accuracy: |
± (1.5% + 3 digits) |
| |
|
| Test Voltage: |
500 V |
| Test Current: |
1 mA @ 500 kΩ |
| Range/Resolution: |
20 MΩ/0.01 MΩ |
| Range/Resolution: |
200 MΩ/0.1 MΩ |
| Accuracy: |
± (1.5% + 3 digits) |
| Range/Resolution: |
500 MΩ/1 MΩ |
| Accuracy: |
10% |
| |
|
| Test Voltage: |
1000 V |
| Test Current: |
1 mA @ 1 MΩ |
| Range/Resolution: |
20 MΩ/0.01 MΩ |
| Range/Resolution: |
200 MΩ/0.1 MΩ |
| Accuracy: |
± (1.5% + 3 digits) |
| Range/Resolution: |
500 MΩ/1 MΩ |
| Accuracy: |
10% |
| |
|
| Auto Discharge: |
Discharge time constant, 0.5 second for C = 1 µF or less |
| Live Circuit Detection: |
Inhibits test if terminal voltage > 30 V prior to initiation of test |
| Maximum Capacitive Load: |
Operable with the 5 µF load |
| | Loop Impedance Measurement (High Current Mode and Non-Trip Mode) |
| Range: |
100 - 500 VAC (50/60 Hz) |
| Input connection: |
Soft Key selection |
| Loop impedance: |
Phase to earth |
| Line impedance: |
Phase to neutral |
| Limit on consecutive tests: |
Automatic thermal shutdown after 50 consecutive tests at 10 second intervals (typical) |
|
|
| Max. Test Current High Current Mode: |
|
| Non-Trip Mode: |
|
|
|
| Range/Resolution: |
20 Ω/0.01 Ω |
| Range/Resolution: |
200 Ω/0.1 Ω |
| Range/Resolution: |
2000 Ω/1 Ω |
|
|
| Accuracy (no Trip mode): |
± (3% + 6 digits) |
| Accuracy (Hi Current mode): |
± (2% + 4 digits) |
| | PFC, PSC Test |
| Computation: |
PFC or PSC determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance |
| Range: |
0 - 25 kA |
| Resolution (Ik < 1000 A): |
1 A |
| Resolution (Ik >= 1000 A): |
0.1 kA |
| Accuracy: |
Determined by accuracy of loop resistance and mains voltage measurements. |
| | RCD Testing ¹ |
| Fluke 1651B |
AC, G, S |
| Fluke 1652B |
AC, G, S, A |
| Fluke 1653B |
AC, G, S, A |
| | Tripping Time Test (?T) |
| Trip Time Accuracy |
±(1% Reading + 1 digit) |
|
|
| Multiplier: |
x ½ |
| Current Settings: |
10, 30, 100, 300, 500, 1000 mA |
| Current Accuracy: |
+0% - 10% |
| RCD Type ¹: |
G |
| Measurement Range: |
310 ms (Europe), 2000 ms (UK) |
| RCD Type ¹: |
S |
| Measurement Range: |
510 ms (Europe), 2000 ms (UK) |
|
|
| Multiplier |
x 1 |
| Current Settings: |
10, 30, 100, 300, 500, 1000 mA |
| Current Accuracy: |
+10% - 0% |
| RCD Type ¹: |
G |
| Measurement Range: |
310 ms |
| RCD Type ¹: |
S |
| Measurement Range: |
510 ms |
|
|
| Multiplier: |
x 5 |
| Current Settings: |
10, 30 mA |
| Current Accuracy: |
±10% |
| RCD Type ¹: |
G |
| Measurement Range: |
50 ms |
| RCD Type ¹: |
S |
| Measurement Range: |
160 ms |
| | Tripping Current (ramp) Test - Fluke 1652B, Fluke 1653B |
| Current Range: |
50% - 110% of RCD's rated current |
| Step Size: |
10% of IΔN |
| Dwell time (Type G): ¹ |
300 ms / step |
| Dwell time (Type S): ¹ |
500 ms / step |
| Trip Current Measurement Accuracy: |
±5% |
| | Earth Resistance Test (RE) - Fluke 1653B |
| Range/Resolution: |
200 Ω/0.1 Ω |
| Accuracy: |
±(2% + 5 digits) |
| Range/Resolution: |
2000 Ω/1 Ω |
| Accuracy: |
±(3.5% + 10 digits) |
| Frequency: |
128 Hz |
| Compliance Voltage: |
+25 V |
| | Phase Sequence Indication - Fluke 1653B |
| Icon: |
Icon Phase Sequence indicator is active |
| Display of Phase Sequence: |
|
|
Displays ‘1-2-3’ in digital display field for correct sequence. |
|
Displays ‘3-2-1’ for incorrect phase. |
|
Dashes in place of a number indicate a valid determination could not be made. |
| | ¹ RCD Types |
| G |
General, no delay |
| S |
Time delay |
| A |
Responds to pulsed signal |
| AC |
Responds to AC |
|
| Environmental Specifications |
| Operating Temperature | | | Humidity (Without Condensation) |
| 10 to 30 °C: |
95% |
| 30 to 40 °C: |
75% |
|
| Safety Specifications |
| Safety Rating |
|
EN 61010-I CAT III 500V, CAT IV 300V |
|
| Mechanical & General Specifications |
| Size |
| (L x W x H): |
10 x 25 x 12.5 cm |
| | Weight | | | Batteries | | | Warranty | | | Battery type |
|
Alkaline supplied, usable with 1.2V NiCD or NiMH rechargeable batteries |
|
|
| Model name | Description | Price Lists | | Fluke 1653B | Multifunction Installation Tester
All models include:
- 6 AA Cell batteries
- C1600 Hard carrying case
- Zero Adapter
- Mains test cord
- TL165X/UK Fused Test Lead Set
- Padded carrying strap
- Quick reference guide
- TP165X Remote control probe and lead¹
- Users manual on CD-ROM
|
¹ In the United Kingdom and Ireland: 1652B & 1653B only
| £ 1,091 | | Fluke 1652B | Multifunction Installation Tester
| £ 878 | | Fluke 1651B | Multifunction Installation Tester
| £ 699 |
|
|
|
|